Error Code:
Error in
receiving serial communication signal (Signal from main indoor
unit in case of group control) Auto address is not completed
Outdoor system address, indoor system address, or indoor unit
individual/main/sub setting is not set (Automatic address setting
is not completed)
|
E01
|
Error in
transmitting serial communication signal
|
E02
|
Indoor unit is
detecting error signal from remote controller (and system
controller)
|
E03
|
Indoor unit
address setting is duplicated
|
E08
|
Remote
controller setting is duplicated
|
E09
|
Error in
transmitting serial communications signal
|
E10
|
Error in
receiving serial communications signal
|
E11
|
Main unit
duplication in simultaneous-operation multi control (detected by
outdoor unit)
|
E14
|
Error in
receiving serial communications signal
|
E04
|
Error in
transmitting serial communications signal
|
E05
|
Error in
receiving serial communications signal (including unit quantity
verification failure)
|
E06
|
Error in
transmitting serial communications signal
|
E07
|
Indoor unit
capacity too low
|
E15
|
Indoor unit
capacity too high
|
E16
|
No indoor
units connected
|
E20
|
Error in
transmitting serial communications signal
|
E17
|
Error in
receiving serial communications signal
|
E18
|
Communications
failure with MDC
|
E31
|
|
|
Indoor unit
group settings error
|
L01
|
Indoor/outdoor
unit type mismatch
|
L02
|
Main unit
duplication in group control (detected by indoor unit)
|
L03
|
Outdoor unit
address duplication (system address)
|
L04
|
Group wiring
connected for independent indoor unit
|
L07
|
Address not
set or group not set
|
L08
|
Indoor unit
capacity not set
|
L09
|
Outdoor unit
capacity not set or setting error
|
L10
|
|
|
Miswiring in
group control wiring
|
L11
|
Indoor unit
type setting error (capacity)
|
L13
|
Ceiling panel
connection failure
|
P09
|
Fan protective
thermostat
|
P01
|
Float switch
|
P10
|
Discharge
temperature trouble
|
P03
|
Open phase
detected, AC power trouble
|
P05
|
No gas
|
P15
|
4-way valve
locked
|
P19
|
High cooling
load
|
P20
|
Outdoor fan
trouble
|
P22
|
Inverter
compressor trouble (HIC PCB)
|
P26
|
Inverter
compressor trouble (MDC)
|
P29
|
Simultaneous-operation
multi control trouble
|
P31
|
Compressor
current failure (overload)
|
H01
|
Indoor heat
exchanger temperature sensor (E1)
|
F01
|
Indoor heat
exchanger temperature sensor (E2)
|
F02
|
Indoor
temperature sensor
|
F10
|
Discharge
temperature (TD)
|
F04
|
Outdoor heat
exchanger temperature (C1)
|
F06
|
Outdoor heat
exchanger temperature (C2)
|
F07
|
Outdoor air
temperature (TO)
|
F08
|
Intake
temperature (TS)
|
F12
|
Indoor EEPROM
error
|
F29
|
Outdoor EEPROM
error
|
F31
|
Remote
controller alarm display
|
Alarm
contents
|
Judgment
condition
|
Clear
condition
|
Judgment
and correction
|
|
P03
|
Abnormal
discharge temperature •Discharge temp. detected at or above the
specified value.
|
Stops when
temp. exceeds 111°C.
|
Recovery at
restart
|
1. Check
refrigerant cycle (gas leak). 2. Electronic control valve trouble
3. Check tubing sensor (TD).
|
P05
|
Missing phase
detected. (CT disconnected or AC power trouble)
|
Current value
sent from MDC on outdoor unit control PCB is low. No AC power
input for 3 minutes or longer: pre-trip - 5
|
Recovery at
restart
|
1. Check R/S/T
power. 2. Check inverter control PCB. 3. Check outdoor unit
control PCB.
|
P15
|
Insufficient
gas level detected.
|
The following
conditions continue for 1 minute. •Discharge temp. is 95°C or
higher. •Electronic control valve is at step 480. •Current
value from MDC is 1.7 A (3-phase) or 1.0 A (1-phase) or less.
|
Recovery at
restart
|
Check
refrigerant cycle (gas leak).
|
P19
|
4-way valve
locked •Judgment occurs after compressor has been ON for 5
minutes.
|
Indoor heat
exchanger temp. drops although compressors are ON in heating mode:
[min(E1, E2)] ≤10°C. Indoor heat exchanger temp. rises
although compressors are ON in cooling mode: E2 ≥40°C
|
Recovery at
restart
|
1. Check 4-way
valve. 2. Check 4-way valve wiring. 3. Check outdoor unit control
PCB.
|
P20
|
High-pressure
protection trouble detected from cooling high-load C2 temp.
|
Temp. exceeds
64°C and subsequently does not drop to 55°C or below.
•Continuously for 30 seconds →Alarm is output when this
occurs once. •Continuously for less than 30 seconds
→Inverter stops.
|
Recovery at
restart
|
1. Refrigerant
cycle overload operation 2. Outdoor coil temperature sensor C2
|
P22
|
Outdoor unit
fan motor trouble •Inverter protection circuit was activated, or
lock was detected, at outdoor unit fan motor.
|
Inverter stops
after alarm is detected
|
Recovery at
restart
|
1. Position
detection trouble 2. Overcurrent protection circuit at outdoor
unit fan motor was activated. •Check outdoor unit control PCB.
•Refer to outdoor unit fan judgment methods.
|
P26
|
Inverter
protection circuit was activated, or G-Tr short-circuit (short
time: 0.8 s or less) in inverter control
|
Inverter stops
after alarm is detected. Alarm is output when inverter stops
(pre-trip) consecutively 4 times.
|
Recovery at
restart
|
1. Stops
immediately when restarted. •Layer short in the compressor 2.
Check inverter control PCB. •Wiring trouble
|
|
Remote
controller alarm display
|
Alarm
contents
|
Judgment
condition
|
Clear
condition
|
Judgment
and correction
|
P29
|
Current
detection circuit trouble •AC current value is high even when
compressor is stopped.
|
Inverter stops
after alarm is detected. Alarm is output when inverter stops
(pre-trip) consecutively 4 times.
|
Recovery at
restart
|
1. Stops
immediately when restarted. •Layer short in the compressor 2.
Check inverter control PCB. •Wiring trouble
|
Compressor
motor output trouble, Inverter compressor trouble, MDC trouble
|
Inverter stops
after alarm is detected.
|
Recovery at
restart
|
1. Refrigerant
cycle trouble, overload operation 2. Loose screws and contact
failure between HIC control PCB and radiating plate 3. Cooling
failure of radiating plate 4. Check outdoor unit PCB wiring.
|
Compressor
does not run. (Overcurrent protection circuit activates after a
certain period of time following compressor start.)
|
Inverter stops
after alarm is detected.
|
Recovery at
restart
|
1. Compressor
trouble (locked, etc.) •Replace the compressor. 2. Compressor
wiring trouble (missing phase)
|
Compressor
breakdown •Starts to operate but operating frequency drops and
compressor stops.
|
Inverter stops
after alarm is detected.
|
Recovery at
restart
|
1. Check power
voltage: AC 200 V ±20 V. 2. Refrigerant cycle overload operation
3. Check AC current detection circuit.
|
Inverter
control PCB position detection circuit trouble
|
Inverter stops
after alarm is detected.
|
Recovery at
restart
|
Position
detection circuit is activated even when the compressor 3P
connector is disconnected and the compressor operated. • Replace
the inverter control PCB.
|
F04
|
Disconnection,
open circuit, or short circuit in discharge temp. sensor (TD)
|
Sensor
detection trouble (90°C or higher when 15 minutes have elapsed
after compressor stopped). (Open circuit)
|
Automatic
recovery
|
1. Check
discharge temp. sensor (TD). 2. Check outdoor unit control PCB.
|
F06
|
Disconnection,
open circuit, or short circuit in outdoor heat exchanger temp.
sensor (C1)
|
Open circuit
or short circuit
|
Automatic
recovery
|
1. Check
outdoor heat exchanger temp. sensor (C1). 2. Check outdoor unit
control PCB.
|
F07
|
Disconnection,
open circuit, or short circuit in outdoor heat exchanger temp.
sensor (C2)
|
Open circuit
or short circuit
|
Automatic
recovery
|
1. Check
outdoor heat exchanger temp. sensor (C2). 2. Check outdoor unit
control PCB.
|
F08
|
Disconnection,
open circuit, or short circuit in outdoor air temp. sensor (TO)
|
Open circuit
or short circuit
|
Automatic
recovery
|
1. Check
outdoor air temp. sensor (TO). 2. Check outdoor unit control PCB.
|
F12
|
Disconnection,
open circuit, or short circuit in intake temp. sensor (TS)
|
Open circuit
or short circuit
|
Automatic
recovery
|
1. Check
intake temp. sensor (TS). 2. Check outdoor unit control PCB.
|
Remote
controller alarm display
|
Alarm
contents
|
Judgment
condition
|
Clear
condition
|
Judgment
and correction
|
|
F31
|
EEPROM trouble
|
Reading/writing
failure
|
Recovery at
power reset
|
1. Check
EEPROM (IC901). 2. Check outdoor unit control PCB.
|
L02
|
Mismatch of
indoor and outdoor unit types (Espacio, Multi, GHP)
|
Indoor unit
judges that type does not match outdoor unit type.
|
Recovery at
power reset
|
1. Check
indoor unit EEPROM. 2. Check indoor unit control PCB.
|
L04
|
Settings
failure
|
Duplicated
outdoor unit address (system address)
|
Automatic
recovery
|
1. Check
outdoor unit system address. 2. Check inter-unit control wiring.
|
L07
|
Settings
failure
|
Group control
wiring is connected to an independent-control indoor
|
Recovery at
power reset
|
1. Check
inter-unit control wiring. 2. Check indoor unit EEPROM.
|
L10
|
Settings
failure
|
Outdoor unit
capacity not set.
|
Recovery at
power reset
|
Check outdoor
unit EEPROM.
|
L13
|
Indoor-outdoor
unit types
|
Outdoor unit
judges that type does not match indoor unit type.
|
Recovery at
power reset
|
1. Check
indoor unit EEPROM. 2. Check outdoor unit control PCB.
|
E06
|
Outdoor unit
detected abnormal signal from indoor unit.
|
Serial signal
receiving failure (including failure to verify No. of units)
|
Automatic
recovery
|
1. Check
inter-unit control wiring. 2. Check outdoor unit
|
E07
|
Outdoor unit
sending failure to indoor unit
|
Serial signal
sending failure
|
Automatic
recovery
|
1. Check
inter-unit control wiring. 2. Check outdoor unit control PCB.
|
E14
|
Settings
failure
|
Duplicated
master unit in simultaneous-operation multi control (Detected by
outdoor unit)
|
Recovery at
power reset
|
1. Check
inter-unit control wiring. 2. Check indoor unit combination.
|
|
E15
|
Automatic
address setting failure
|
Indoor unit
capacity too low.
|
Recovery at
power reset
|
1. Check
inter-unit control wiring. 2. Check outdoor unit control PCB.
|
|
E16
|
Automatic
address setting failure
|
Indoor unit
capacity too high.
|
Recovery at
power reset
|
1. Check
inter-unit control wiring. 2. Check outdoor unit control PCB.
|
|
E20
|
Automatic
address setting failure
|
Outdoor unit
cannot receive any serial signals from indoor units.
|
Recovery at
power reset
|
1. Check
inter-unit control wiring. 2. Check outdoor unit control PCB.
|
|
E31
|
Communications
trouble within unit
|
No
communication possible with MDC for 3 minutes or longer.
|
Automatic
recovery
|
Check outdoor
unit control PCB.
|
|
H01
|
Overcurrent
|
Inverter stops
after alarm is detected.
|
Recovery at
restart
|
1. Refrigerant
cycle trouble, overload operation 2. Loose screws between HIC
control PCB and radiating plate 3. Cooling failure of radiating
plate 4. Check outdoor unit PCB wiring.
|
|
INDOOR
MODEL NO.
|
PRODUCT
CODE NO.
|
SPW-UR124GH56
|
854 021
42
|
SPW-UR164GH56
|
854 021
43
|
SPW-UR184GH56
|
854 021
44
|
SPW-UR254GH56
|
854 021
45
|
SPW-UR364GH56
|
854 021
46
|
SPW-UR484GH56
|
854 021
47
|
|
|
OUTDOOR
MODEL NO.
|
PRODUCT
CODE NO.
|
SPW-CR254GV56-C
|
854 021
29
|
SPW-CR254GVH56-C
|
854 021
26
|
SPW-CR364GV56-C
|
854 021
30
|
SPW-CR364GVH56-C
|
854 021
27
|
SPW-CR484GV56-C
|
854 021
31
|
SPW-CR484GVH56-C
|
854 021
28
|
|
INDOOR
MODEL NO.
|
PRODUCT
CODE NO.
|
SPW-XDR124GH56
|
854 021
36
|
SPW-XDR164GH56
|
854 021
37
|
SPW-XDR184GH56
|
854 021
38
|
SPW-XDR254GH56
|
854 021
39
|
SPW-XDR364GH56
|
854 021
40
|
SPW-XDR484GH56
|
854 021
41
|
SPW-KR124GH56
|
854 021
54
|
SPW-KR164GH56
|
854 021
55
|
SPW-KR184GH56
|
854 021
56
|
SPW-KR254GH56
|
854 021
57
|
SPW-TDR124GH56
|
854 021
48
|
SPW-TDR164GH56
|
854 021
49
|
SPW-TDR184GH56
|
854 021
50
|
SPW-TDR254GH56
|
854 021
51
|
SPW-TDR364GH56
|
854 021
52
|
SPW-TDR484GH56
|
854 021
53
|
|
Combination of
Indoor and Outdoor Units:
SPW-XDR124GH56 X 2 /
SPW-CR254GV56 SPW-TDR124GH56 X 2 / SPW-CR254GV56
SPW-XDR124GH56 X 2 /
SPW-CR254GVH56 SPW-TDR124GH56 X 2 / SPW-CR254GVH56
SPW-XDR124GH56 X 4 /
SPW-CR484GV56 SPW-TDR124GH56 X 4 / SPW-CR484GV56
SPW-XDR124GH56 X 4 /
SPW-CR484GVH56 SPW-TDR124GH56 X 4 / SPW-CR484GVH56
SPW-XDR164GH56 X 3 /
SPW-CR484GV56 SPW-TDR164GH56 X 3 / SPW-CR484GV56
SPW-XDR164GH56 X 3 /
SPW-CR484GVH56 SPW-TDR164GH56 X 3 / SPW-CR484GVH56
SPW-XDR184GH56 X 2 /
SPW-CR364GV56 SPW-TDR184GH56 X 2 / SPW-CR364GV56
SPW-XDR184GH56 X 2 /
SPW-CR364GVH56 SPW-TDR184GH56 X 2 / SPW-CR364GVH56
SPW-XDR254GH56 /
SPW-CR254GV56 SPW-TDR254GH56 / SPW-CR254GV56
SPW-XDR254GH56 /
SPW-CR254GVH56 SPW-TDR254GH56 / SPW-CR254GVH56
SPW-XDR254GH56 X 2 /
SPW-CR484GV56 SPW-TDR254GH56 X 2 / SPW-CR484GV56
SPW-XDR254GH56 X 2 /
SPW-CR484GVH56 SPW-TDR254GH56 X 2 / SPW-CR484GVH56
SPW-XDR364GH56 /
SPW-CR364GV56 SPW-TDR364GH56 / SPW-CR364GV56
SPW-XDR364GH56 /
SPW-CR364GVH56 SPW-TDR364GH56 / SPW-CR364GVH56
SPW-XDR484GH56 /
SPW-CR484GV56 SPW-TDR484GH56 / SPW-CR484GV56
SPW-XDR484GH56 /
SPW-CR484GVH56 SPW-TDR484GH56 / SPW-CR484GVH56
SPW-UR124GH56 X 2 /
SPW-CR254GV56 SPW-KR124GH56 X 2 / SPW-CR254GV56
SPW-UR124GH56 X 2 /
SPW-CR254GVH56 SPW-KR124GH56 X 2 / SPW-CR254GVH56
SPW-UR124GH56 X 4 /
SPW-CR484GV56 SPW-KR124GH56 X 4 / SPW-CR484GV56
SPW-UR124GH56 X 4 /
SPW-CR484GVH56 SPW-KR124GH56 X 4 / SPW-CR484GVH56
SPW-UR164GH56 X 3 /
SPW-CR484GV56 SPW-KR164GH56 X 3 / SPW-CR484GV56
SPW-UR164GH56 X 3 /
SPW-CR484GVH56 SPW-KR164GH56 X 3 / SPW-CR484GVH56
SPW-UR184GH56 X 2 /
SPW-CR364GV56 SPW-KR184GH56 X 2 / SPW-CR364GV56
SPW-UR184GH56 X 2 /
SPW-CR364GVH56 SPW-KR184GH56 X 2 / SPW-CR364GVH56
SPW-UR254GH56 /
SPW-CR254GV56 SPW-KR254GH56 / SPW-CR254GV56
SPW-UR254GH56 /
SPW-CR254GVH56 SPW-KR254GH56 / SPW-CR254GVH56
SPW-UR254GH56 X 2 /
SPW-CR484GV56 SPW-KR254GH56 X 2 / SPW-CR484GV56
SPW-UR254GH56 X 2 /
SPW-CR484GVH56 SPW-KR254GH56 X 2 / SPW-CR484GVH56
SPW-UR364GH56 /
SPW-CR364GV56
SPW-UR364GH56 /
SPW-CR364GVH56
SPW-UR484GH56 /
SPW-CR484GV56
SPW-UR484GH56 /
SPW-CR484GVH56
Links:
Sanyo
GHP Gas Service Kit
Sanyo
Air Conditioning SPW error codes
Sanyo
SAP Fault Codes
Contact
Us:
Sales
UK: +44 (0)1234 841221
Tel UK: 01234 841221
Fax: +44 (0)1234 852662
Address:
Orion Air Conditioning And Refrigeration Limited
10 Grisedale Court
Woburn Road Industrial Estate
Kempston
Bedfordshire
MK42 7EE
United Kingdom
Orion
air conditioning and refrigeration limited is a United Kingdom based
distributor of environmental products including air conditioning,
heat pumps, electric space heaters, gas space heaters, oil space
heaters, air exchange units, dehumidifiers and refrigeration equipment.
Since
2005 we have offered our expertise and quality service backup
to clients in the UK and overseas with a team of global
distribution experts in house. With a huge range of equipment to offer
we supply leading businesses, governments, the HVAC
trade and end users with quality branded product.
Residential,
commercial and industrial heaters. Portable and fixed space heaters
with something for everyone from the 500W to 100kw. We have one of the
most extensive heater selections from patio heaters, fire places,
propane heaters, oil filled radiators, fan heaters, oil heaters,
gas heaters and infrared.
Wall
mounted air conditioning is the most popular type of air conditioning
system. Versatile and easy to install, most wall air conditioning units
have a filter which destroys funghi, collects duct in the air, bacteria
and viruses which provides healthy clean air for the occupants. Modern
wall air conditioning units have Innovative inverter
compressor designs and the ozone friendly R410A and R32
refrigerants combined with low noise air movement fan arrangement. The
result is a quiet, high performance cooling and heating system,
with advanced electronic controls for maximum comfort, controllable and
energy efficient.
The
Olympus Appliances JetHeat series of portable commercial / industrial
electric fan heaters are designed for use in workshops, schools,
warehouses, nurseries, showrooms, storage rooms, construction sites and
containers. This series is made to a high standard and features a 3Kw /
240V and 9Kw / 415V, 15Kw / 415V and the largest 30Kw in 3 phase 415V
format.
Designed
to give the greatest possible safety, performance and reliability even
in the most demanding industrial and commercial
applications. Housed within the high-grade steel bodies and sickle
bladed fans, designed to maximise airflow and pressure, which are driven
by aluminium motors that keep weight to a minimum. Ideal for
ventilation, extraction and fresh air supply as well as dust and
fume extraction. Available in standard and explosion proof 110V and
240V~50Hz.
Projects
And Tendering:
Server
room air conditioning systems that save electricity, make
inverter air conditioning your priority.
|
Specialist
air conditioning and refrigeration systems for industrial
applications.
|
Tendering
on a project and need advice on a quotation? Contact our sales
team today.
Tender
request
|
Orion
air conditioning and refrigeration offer an UK installation,
service and maintenance on Industrial, commercial refrigeration and air
conditioning. Spare
parts supply on Bitzer, Copeland, Prescold, Carrier, Carlyle, Dorin,
Prescold, Frascold, Gram, Grasso, Hubbard, Maneurop, Trane and Sabroe.
Air
conditioning and refrigeration spare parts from all the manufacturers
including fan blades, thermistor probes, compressors, scroll
compressor, Inverter compressor, swing compressor, Inverter Pcb,
printed circuit boards, air filters, fan motors, thermisters, drain
pumps, remote controls, expansion valve, condensor coil, solenoid
valve, crankcase heater, electronic thermostat, float switch, magnetic
contactor, capacitor, high pressure switch, low pressure switches
and PCB's, PWB's.