Air Conditioning Fault Codes Complete List
ADDRESSING & COMMUNICATION PROBLEMS
Code
|
Description
|
E01
|
Remote control detecting error from
indoor unit, Address not set/Auto address failed. Check
interconnecting wiring etc. Re-address system.
|
|
|
E02
|
Remote detecting error from indoor
unit,
|
E03
|
Indoor unit detecting error from
remote,
|
E04
|
Indoor seeing error from outdoor.
Qty of i/d units connected are less than qty set. Check; all i/d
units are ON,
|
|
reset turn off all units wait 5min
power up
|
E05
|
Indoor unit detecting error from
outdoor unit, Error in sending comms signal
|
E06
|
Outdoor unit detecting error from
indoor unit, Error in receiving comms signal
|
E07
|
Outdoor unit detecting error from
indoor unit, Error in sending comms signal
|
E08
|
Incorrect setting indoor/controller,
Indoor address duplicated
|
E09
|
Incorrect setting indoor/controller,
Remote address duplicated or IR wireless controller not disabled
|
E10
|
Indoor unit detecting error from
'option' plug, Error in sending comms signal
|
E11
|
Indoor unit detecting error from
'option' plug, Error in receiving comms signal
|
E12
|
Auto addressing failed,Auto address
connector CN100 shorted during auto addressing
|
E13
|
Indoor unit failed to send signal to
remote controller
|
E14
|
Setting Failure, Duplication of
master indoor units
|
E15
|
Auto addressing failed, Number of
indoor units connected are less than number set
|
E16
|
Auto addressing failed, Number of
indoor units connected are more than number set
|
E17
|
Group control wiring error, Main
indoor unit not sending signal for sub indoor units
|
E18
|
Group control wiring error, Main
indoor unit not receiving signal for sub indoor units
|
E20
|
Auto addressing failed, No indoor
units connected
|
E24
|
Auto addressing failed, Error on sub
outdoor unit
|
E25
|
Auto addressing failed, Error on
outdoor unit address setting
|
E26
|
Auto addressing failed, Quantity of
main and sub outdoor units do not correspond to the number set on
main
|
|
outdoor unit P.C.B.
|
E29
|
Auto addressing failed, Sub outdoor
unit not receiving comms for main outdoor unit
|
E31
|
Between units, Comms failure with
MDC, does E31 remain after power is re instated? If so replace
PCB. & power
|
|
PCB
|
Senior Faults
Code
|
Description
|
F01
|
Indoor Heat Exch inlet temp sensor
failure (E1)
|
F02
|
Indoor Heat Exch freeze temp sensor
failure (E2)
|
F03
|
Indoor Heat Exch outlet temp sensor
failure (E3)
|
F04
|
Outdoor Discharge temp sensor
failure (TD) or (DISCH1)
|
F05
|
Outdoor Discharge temp sensor
failure (DISCH2)
|
F06
|
Outdoor Heat Exch temp sensor
failure (C1) or (EXG1)
|
F07
|
Outdoor Heat Exch temp sensor
failure (C2) or (EXL1)
|
F08
|
Outdoor Air temp sensor failure (TO)
|
F10
|
Indoor inlet temp sensor failure
|
F11
|
Indoor outlet temp sensor failure
|
F12
|
Outdoor Intake sensor failure (TS)
|
F13
|
GHP - Cooling water temperature
sensor failure
|
F16
|
Outdoor High pressure sensor failure
|
F17
|
GHP - Cooling water temperature
sensor fault
|
F18
|
GHP - Exhaust gas temperature sensor
fault
|
F20
|
GHP Clutch coil temperature fault
|
F23
|
Outdoor Heat Exch temp sensor
failure (EXG2)
|
F24
|
Outdoor Heat Exch temp sensor
failure (EXL2)
|
F29
|
Indoor EEPROM error
|
F30
|
Clock Function (RTC) fault
|
F31
|
Outdoor EEPROM error
|
Compressor Faults
Code
|
Description
|
H01
|
Compressor Fault, Over current
(Comp1)
|
H02
|
Compressor Fault, Locked rota
current detected (Comp1)
|
H03
|
Compressor Fault, No current
detected (Comp1)
|
H05
|
Compressor Fault, Discharge temp not
detected (Comp1)
|
H06
|
Compressor Fault, Low Pressure trip
|
H07
|
Compressor Fault, Low oil level
|
H08
|
Compressor Fault, Oil sensor Fault
(Comp1)
|
H11
|
Compressor Fault, Over current
(Comp2)
|
H12
|
Compressor Fault, Locked rota
current detected (Comp2)
|
H13
|
Compressor Fault, No current
detected (Comp2)
|
H15
|
Compressor Fault, Discharge temp not
detected (Comp2)
|
H27
|
Compressor Fault, Oil sensor fault
(Comp2)
|
H28
|
Compressor Fault. Oil sensor
(connection failure)
|
H31
|
Compressor Fault. IPM trip (IMP
current on temperature)
|
Incorrect Settings
Code
|
Description
|
L01
|
Setting Error, Indoor unit group
setting error
|
L02
|
Setting Error, Indoor/outdoor unit
type/model miss-matched
|
L03
|
Duplication of main indoor unit
address in group control
|
L04
|
Duplication of outdoor unit system
address
|
L05
|
2 or more controllers have been set
as 'priority' in one system - shown on controllers set as
'priority'
|
L06
|
2 or more controllers have been set
as 'priority' in one system - shown on controllers not set as
'priority'
|
L07
|
Group wiring connected on and
indvidual indoor unit
|
L08
|
Indoor unit address/group not set
|
L09
|
Indoor unit capacity code not set
|
L10
|
Outdoor unit capacity code not set
|
L11
|
Group control wiring incorrect
|
L13
|
Indoor unit type setting error,
capacity
|
L15
|
Indoor unit paring fault
|
L16
|
Water heat exch unit setting failure
|
L17
|
Miss-match of outdoor unit with
different refrigerant
|
L18
|
4-way valve failure
|
L19
|
Water heat exch unit duplicated
address
|
L21
|
Gas type setup failure
|
Indoor Faults
Code
|
Description
|
P01
|
Indoor unit fault, Fan motor thermal
overload
|
P02
|
Outdoor unit fault, Compressor motor
thermal overload, over or under voltage
|
P03
|
Outdoor unit fault, Compressor
discharge temperature too high (Comp1) over 111 degC. Low on ref
gas, exp
|
|
valve, pipework damage.
|
P04
|
Outdoor unit fault, High pressure
trip
|
P05
|
Outdoor unit fault, Open phase on
power supply. Check power on each phase, inverter pcb, control pcb
|
P09
|
Indoor unit fault, Ceiling panel
incorrectly wired
|
P10
|
Indoor unit fault, Condensate float
switch opened
|
P11
|
GHP - Water Heat exch low temp
(frost protection) fault
|
P12
|
Indoor unit fault, Fan DC motor
fault
|
P14
|
Input from leak detector (If fitted)
|
P15
|
Refrigerant loss, high discharge
temp and EEV wide open and low compressor current draw.
|
P16
|
Outdoor unit fault, Open phase on
compressor power supply
|
P17
|
Outdoor unit fault, Compressor
discharge temperature too high (Comp2) over 111 degC. Low on ref
gas, exp
|
|
valve, pipework damage.
|
P18
|
Outdoor unit fault, By-pass valve
failure
|
P19
|
Outdoor unit fault, 4 way valve
failure, i/door temp rises in cooling or fulls in heating. Check
wiring, coil, pcb output,
|
|
valave operation.
|
P20
|
Ref gas, high temp/pressure fault,
heat exch temp high C2, 55-60 degC, cooling over-load, sensor
fault.
|
P22
|
Outdoor unit fan motor fault, fan
blade jammed, check connections, does fan turn freely, motor
resistance 30-
|
|
40ohm on each pair, no fan fault,
yes pcb fault.
|
P26
|
Outdoor unit fault, Compressor
overcurrent - check winding resistance, Inverter failure - check
internal resistance
|
|
term HIC + & - to UVW
200-300Kohm or more
|
P29
|
Outdoor unit fault, Inverter circuit
fault - Motor-current Detection Circuit (MDC) fault, check comp
windings, sen-
|
|
sors C1 & TS, if ok possible pcb
failure.
|
P30
|
Indoor unit fault, System controller
detected fault on sub indoor unit
|
P31
|
Simultaneous operation multi control
fault, Group controller fault
|
GHP Fault Code Description
A01 GHP - Engine oil pressure fault
A02 GHP - Engine oil level fault
A03 GHP - Engine over speed
A04 GHP - Engine under speed
A05 GHP - Ignition power supply failure
A06 GHP - Engine start up failure
A07 GHP - Fuel gas valve failure
A08 GHP - Engine stalled
A09 GHP - Engine overload
A10 GHP - High exhaust gas temp
A11 GHP - Engine oil level failure
A12 GHP - Throttle actuator fault
A13 GHP - Fuel gas valve adjustment failure
A14 GHP - Engine oil pressure sensor fault
A15 GHP - Starter power output short circuit
A16 GHP - Starter motor locked
A17 GHP - Starter current (CT) coil failed
A19 GHP - Wax Valve (3 Way) fault
A20 GHP - Cooling water temp high
A21 GHP - Cooling water level fault
A22 GHP - Cooling water pump fault
A23 GHP - Engine crank angle sensor failure
A24 GHP - Engine cam angle sensor failure
A25 GHP - Clutch fault
A26 GHP - Misfire
A27 GHP - Catalyst temperature fault
A28 GHP - Generator fault
A29 GHP - Converter fault
A30 GHP - Fuel gas pressure low
Links:
Sanyo
GHP Gas Service Kit
Sanyo
Air Conditioning SPW error codes
Sanyo
SAP Fault Codes
Spare Parts: +44 (0)1234 841221
Tel UK: 01234 841221
Fax: +44 (0)1234 852662
Address:
Orion Air Conditioning And Refrigeration Limited
10 Grisedale Court
Woburn Road Industrial Estate
Kempston
Bedfordshire
MK42 7EE
United Kingdom
Email: [email protected]
Orion
air conditioning and refrigeration limited is a United Kingdom based
distributor of environmental products including air conditioning,
heat pumps, electric space heaters, gas space heaters, oil space
heaters, air exchange units, dehumidifiers and refrigeration equipment.
Since
2005 we have offered our expertise and quality service backup
to clients in the UK and overseas with a team of global
distribution experts in house. With a huge range of equipment to offer
we supply leading businesses, governments, the HVAC
trade and end users with quality branded product.
Residential,
commercial and industrial heaters. Portable and fixed space heaters
with something for everyone from the 500W to 100kw. We have one of the
most extensive heater selections from patio heaters, fire places,
propane heaters, oil filled radiators, fan heaters, oil heaters,
gas heaters and infrared.
Wall
mounted air conditioning is the most popular type of air conditioning
system. Versatile and easy to install, most wall air conditioning units
have a filter which destroys funghi, collects duct in the air, bacteria
and viruses which provides healthy clean air for the occupants. Modern
wall air conditioning units have Innovative inverter
compressor designs and the ozone friendly R410A and R32
refrigerants combined with low noise air movement fan arrangement. The
result is a quiet, high performance cooling and heating system,
with advanced electronic controls for maximum comfort, controllable and
energy efficient.
The
Olympus Appliances JetHeat series of portable commercial / industrial
electric fan heaters are designed for use in workshops, schools,
warehouses, nurseries, showrooms, storage rooms, construction sites and
containers. This series is made to a high standard and features a 3Kw /
240V and 9Kw / 415V, 15Kw / 415V and the largest 30Kw in 3 phase 415V
format.
Designed
to give the greatest possible safety, performance and reliability even
in the most demanding industrial and commercial
applications. Housed within the high-grade steel bodies and sickle
bladed fans, designed to maximise airflow and pressure, which are driven
by aluminium motors that keep weight to a minimum. Ideal for
ventilation, extraction and fresh air supply as well as dust and
fume extraction. Available in standard and explosion proof 110V and
240V~50Hz.
Projects
And Tendering:
Server
room air conditioning systems that save electricity, make
inverter air conditioning your priority.
|
Specialist
air conditioning and refrigeration systems for industrial
applications.
|
Tendering
on a project and need advice on a quotation? Contact our sales
team today.
Tender
request
|
Orion
air conditioning and refrigeration offer an UK installation,
service and maintenance on Industrial, commercial refrigeration and air
conditioning. Spare
parts supply on Bitzer, Copeland, Prescold, Carrier, Carlyle, Dorin,
Prescold, Frascold, Gram, Grasso, Hubbard, Maneurop, Trane and Sabroe.
Air
conditioning and refrigeration spare parts from all the manufacturers
including fan blades, thermistor probes, compressors, scroll
compressor, Inverter compressor, swing compressor, Inverter Pcb,
printed circuit boards, air filters, fan motors, thermisters, drain
pumps, remote controls, expansion valve, condensor coil, solenoid
valve, crankcase heater, electronic thermostat, float switch, magnetic
contactor, capacitor, high pressure switch, low pressure switches
and PCB's, PWB's.