|
Mitsubishi Electric air conditioning in collaboration with
Thermoscreens: Air Curtain Heat-pump Systems 2010
|
In
collaboration with Thermo-screens, Mitsubishi Electric air
conditioning have developed a range of air curtains that are
able to be connected to the Power Inverter heat pumps, as
opposed to the more traditional direct electric method
associated with air curtains. This reduces CO2 emissions/
running costs by up to 67% with a 2.5 year payback period
against equivalent Electric system.
Key
Product Features:
- Reduced CO2
emissions (up to 67%)
- Reduced
Running Costs (up to 67%)
- 2.5 year
payback period against equivalent Electric system
- Inverter
technology (does not waste energy)
- Range of
different sizes to suit every application
- Allows open
door policy in retail outlets whilst being energy
efficient
- Clean
environment - protection from dust, fumes etc
- Comfortable
climate for customers
- Easy to
install and maintain
For e-mail
quotations: Please
enter the model you are interested in here.:
Technical Data:
|
MODEL REFERENCE |
PHV1000R DXE HO |
PHV1500R DXE LO |
PHV1500R DXE HO |
PHV2000R DXE LO |
PHV2000R DXE HO |
DIMENSIONS (mm) (WxDxH) |
1150x436x296 |
1650x436x296 |
1650x436x296 |
2240x436x296 |
2240x436x296 |
SUPPLY (50Hz) |
415V*1 |
415V*1 |
415V*1 |
415V*2 |
415V*2 |
HEAT OUTPUT (kW) |
100% / 50% |
8.6 / 5.34 |
10.1 / 5.6 |
14.4 / 8.3 |
14.1 / 7.9 |
21.3 / 11.2 |
COP |
100% / 50% |
2.4 / 3.15 |
2.3 / 3.4 |
2.5 / 3.7 |
2.9 / 3.7 |
2.4 / 3.2 |
LOADING (amps) |
9.2*1 |
12.7*1 |
12.7*1 |
15.7*2 |
15.7*2 |
VELOCITY (m/s) |
9 |
9 |
9 |
9.5 |
9 |
AIR VOLUME (m3/h) |
1400 |
2500 |
2600 |
3300 |
3130 |
WEIGHT (kg) |
45 |
66 |
67 |
85 |
88 |
dB(A) @ 3m |
100% / 50% |
59 / 57 |
60 / 58 |
60 / 58 |
61 / 59 |
61 / 59 |
MAX. MOUNTING HEIGHT (m) |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
OUTDOOR UNIT MODEL |
PUHZ-RP71VHA4 |
PUHZ-RP71VHA4 |
PUHZ-RP140VKA/YKA |
PUHZ-RP100VKA/YKA |
PUHZ-RP200YKA |
Notes: *1 for units
with electric heaters disabled, 240v power supply 1.8
amp load (1.3 amp load for PHV1000R DXE HO) *2 for units
with electric heaters disabled, 240v power supply 2.7
amp load.
|
|
MODEL REFERENCE |
PHV1000 DXE HO |
PHV1500 DXE LO |
PHV1500 DXE HO |
PHV2000 DXE LO |
PHV2000 DXE HO |
DIMENSIONS (mm) (WxDxH) |
1196x377x255 |
1746x377x255 |
1746x377x255 |
2296x377x255 |
2296x377x255 |
SUPPLY (50Hz) |
415V*1 |
415V*1 |
415V*1 |
415V*2 |
415V*2 |
HEAT OUTPUT (kW) |
100% / 50% |
8.6 / 5.34 |
10.1 / 5.6 |
14.4 / 8.3 |
14.1 / 7.9 |
21.3 / 11.2 |
COP |
100% / 50% |
2.4 / 3.15 |
2.3 / 3.4 |
2.5 / 3.7 |
2.9 / 3.7 |
2.4 / 3.2 |
LOADING (amps) |
9.2*1 |
12.7*1 |
12.7*1 |
15.7*2 |
15.7*2 |
VELOCITY (m/s) |
9 |
9 |
9 |
9.5 |
9 |
AIR VOLUME (m3/h) |
1400 |
2500 |
2600 |
3300 |
3130 |
WEIGHT (kg) |
39 |
59 |
60 |
78 |
80 |
dB(A) @ 3m |
100% / 50% |
59 / 57 |
60 / 58 |
60 / 58 |
61 / 59 |
61 / 59 |
MAX. MOUNTING HEIGHT (m) |
3.75 |
3.75 |
3.75 |
3.75 |
3.75 |
OUTDOOR UNIT MODEL |
PUHZ-RP71VHA4 |
PUHZ-RP71VHA4 |
PUHZ-RP140VKA/YKA |
PUHZ-RP100VKA/YKA |
PUHZ-RP200YKA |
Notes: *1 for units with electric
heaters disabled, 240v power supply 1.8 amp load (1.3
amp load for PHV1000 DXE HO) *2 for units with electric
heaters disabled, 240v power supply 2.7 amp load.
|
|
MODEL REFERENCE |
PUHZ-RP71VHA4 |
PUHZ-RP100VKA/YKA |
PUHZ-RP140VKA/YKA |
PUHZ-RP200YKA |
DIMENSIONS (mm) (WxDxH) |
950x330+30x943 |
1050x330+30x1338 |
1050x330+30x1338 |
1050x330+30x1338 |
SUPPLY (50Hz) |
230V |
230V / 415V |
230V / 415V |
415V |
MAX. CURRENT (A) |
19 |
26.5 / 8 |
28 / 11 |
19 |
FUSE SIZE HRC (BS88) |
20 |
32 / 10 |
32 / 16 |
20 |
MAX. PIPE RUN |
Length (m) |
50 |
50 |
50 |
100 |
|
Height (m) |
30 |
30 |
30 |
30 |
PIPE SIZES |
Gas mm(in) |
15.88 (5/8) |
15.88 (5/8) |
15.88 (5/8) |
28.58 (1 1/8) |
|
Liquid mm(in) |
9.52 (3/8) |
9.52 (3/8) |
9.52 (3/8) |
9.52 (3/8) |
INTERCONNECTING CABLE |
2 core |
2 core |
2 core |
2 core |
|
|
|
|
|