In collaboration with Thermoscreens, Mitsubishi Electric air conditioning have developed a range of air curtains that are able to be connected to the Power Inverter heat pumps, as opposed to the more traditional direct electric method associated with air curtains. This reduces CO2 emissions/ running costs by up to 67% with a 2.5 year payback period against equivalent Electric system.
Key Product Features:
Product Data:
MODEL REFERENCE |
PHV1000R DXE HO |
PHV1500R DXE LO |
PHV1500R DXE HO |
PHV2000R DXE LO |
PHV2000R DXE HO |
|||
DIMENSIONS (mm) (WxDxH) |
1150x436x296 |
1650x436x296 |
1650x436x296 |
2240x436x296 |
2240x436x296 |
|||
SUPPLY (50Hz) |
415V*1 |
415V*1 |
415V*1 |
415V*2 |
415V*2 |
|||
HEAT OUTPUT (kW) |
100% / 50% |
8.6 / 5.34 |
10.1 / 5.6 |
14.4 / 8.3 |
14.1 / 7.9 |
21.3 / 11.2 |
||
COP |
100% / 50% |
2.4 / 3.15 |
2.3 / 3.4 |
2.5 / 3.7 |
2.9 / 3.7 |
2.4 / 3.2 |
||
LOADING (amps) |
9.2*1 |
12.7*1 |
12.7*1 |
15.7*2 |
15.7*2 |
|||
VELOCITY (m/s) |
9 |
9 |
9 |
9.5 |
9 |
|||
AIR VOLUME (m3/h) |
1400 |
2500 |
2600 |
3300 |
3130 |
|||
WEIGHT (kg) |
45 |
66 |
67 |
85 |
88 |
|||
dB(A) @ 3m |
100% / 50% |
59 / 57 |
60 / 58 |
60 / 58 |
61 / 59 |
61 / 59 |
||
MAX. MOUNTING HEIGHT (m) |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
|||
OUTDOOR UNIT MODEL |
PUHZ-RP71VHA4 |
PUHZ-RP71VHA4 |
PUHZ-RP140VKA/YKA |
PUHZ-RP100VKA/YKA |
PUHZ-RP200YKA |
|||
Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load (1.3 amp load for PHV1000R DXE HO) *2 for units with electric heaters disabled, 240v power supply 2.7 amp load. |
MODEL REFERENCE |
PHV1000 DXE HO |
PHV1500 DXE LO |
PHV1500 DXE HO |
PHV2000 DXE LO |
PHV2000 DXE HO |
||
DIMENSIONS (mm) (WxDxH) |
1196x377x255 |
1746x377x255 |
1746x377x255 |
2296x377x255 |
2296x377x255 |
||
SUPPLY (50Hz) |
415V*1 |
415V*1 |
415V*1 |
415V*2 |
415V*2 |
||
HEAT OUTPUT (kW) |
100% / 50% |
8.6 / 5.34 |
10.1 / 5.6 |
14.4 / 8.3 |
14.1 / 7.9 |
21.3 / 11.2 |
|
COP |
100% / 50% |
2.4 / 3.15 |
2.3 / 3.4 |
2.5 / 3.7 |
2.9 / 3.7 |
2.4 / 3.2 |
|
LOADING (amps) |
9.2*1 |
12.7*1 |
12.7*1 |
15.7*2 |
15.7*2 |
||
VELOCITY (m/s) |
9 |
9 |
9 |
9.5 |
9 |
||
AIR VOLUME (m3/h) |
1400 |
2500 |
2600 |
3300 |
3130 |
||
WEIGHT (kg) |
39 |
59 |
60 |
78 |
80 |
||
dB(A) @ 3m |
100% / 50% |
59 / 57 |
60 / 58 |
60 / 58 |
61 / 59 |
61 / 59 |
|
MAX. MOUNTING HEIGHT (m) |
3.75 |
3.75 |
3.75 |
3.75 |
3.75 |
||
OUTDOOR UNIT MODEL |
PUHZ-RP71VHA4 |
PUHZ-RP71VHA4 |
PUHZ-RP140VKA/YKA |
PUHZ-RP100VKA/YKA |
PUHZ-RP200YKA |
||
Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load (1.3 amp load for PHV1000 DXE HO) *2 for units with electric heaters disabled, 240v power supply 2.7 amp load.
|
MODEL REFERENCE |
PUHZ-RP71VHA4 |
PUHZ-RP100VKA/YKA |
PUHZ-RP140VKA/YKA |
PUHZ-RP200YKA |
|||||
DIMENSIONS (mm) (WxDxH) |
950x330+30x943 |
1050x330+30x1338 |
1050x330+30x1338 |
1050x330+30x1338 |
|||||
SUPPLY (50Hz) |
230V |
230V / 415V |
230V / 415V |
415V |
|||||
MAX. CURRENT (A) |
19 |
26.5 / 8 |
28 / 11 |
19 |
|||||
FUSE SIZE HRC (BS88) |
20 |
32 / 10 |
32 / 16 |
20 |
|||||
MAX. PIPE RUN |
Length (m) |
50 |
50 |
50 |
100 |
||||
Height (m) |
30 |
30 |
30 |
30 |
|||||
PIPE SIZES |
Gas mm(in) |
15.88 (5/8) |
15.88 (5/8) |
15.88 (5/8) |
28.58 (1 1/8) |
||||
Liquid mm(in) |
9.52 (3/8) |
9.52 (3/8) |
9.52 (3/8) |
9.52 (3/8) |
|||||
INTERCONNECTING CABLE |
2 core |
2 core |
2 core |
2 core |